TRUE while the timer is running. As per UL 864 and UL 2572 only a setting of 0
is permissible.
o Powerfail Send Delay - if the only trouble on the system is an AC power
failure, transmission of the status through the UDACT can be delayed up to
18 hours. The default is set to 3 hours.
o Proving Circuit Delay - 5-90 seconds. This timer is used for fan dampers, etc.
If the monitor inputs do not activate (indicating that the fan has started
running, or the damper has moved to its commanded position) within the
specified time, then a trouble will be reported and LEDs associated with the
fan damper switch will flash.
o Auto Resound 5-12 minutes. This timer specifies the time after which the
signals will resound. The timer is stopped by (1) new alarm (2) Alarm
Acknowledge or (3) system reset.
o Node Ctrl active timeout 5-10 minutes. Timer is started when a node gets
control. This timer is reset every time a switch belonging to that node is
pressed. When this timer expires the system is automatically brought back to
idle state. Default value is 5 min. For how to use information please refer to
the section Node Control. Note: Node Ctrl active timeout is enabled if Node
Control Enable and Node Ctrl Switch flags (Node Controls section) are set.
o Node Ctrl request timeout 30-60 seconds. Timer is started with every request
for control. When it expires the request for control is canceled if it has not
been granted before the timer expires. Default value is 30 seconds. For how
to use information please refer to the section Node Control. Note: Node Ctrl
request timeout is enabled if Node Control Enable and Node Ctrl Switch flags
(Node Controls section) are set.
• Date and Time
o Daily clock adjustment
Specifies the number of seconds (positive or negative) by which the
panel's clock is to be adjusted every 24 hours. The adjustment, if any, is
made at 01:55 every day.
o Daylight Saving
Enable Daylight Saving - Enables automatic change to and from daylight
saving.
o After Hours
Enable Auto After Hours