95
Dialer
This form is displayed when the optional Dialer tree item is selected. It allows you to view
and to configure the UDACT / Dialer.
The dialer can dial out on two phone lines. You must configure an account and specify the
line attributes for both. Line 2 can dial a cell phone. If this is the case the auto test can be
reduced from daily to monthly.
The UDACT can be configured either by using the FX-2000NConfig tool or with the Mircom
Dialer Configuration Utility.
To configure using the FX-2000NConfig utility remove the RS485 / UIMA cable from the
FX2000N panel and plug it directly to the dialer. You must short JW2 on the dialer to enable
configuration. Edit the dialer parameters, described below, and press the Send... button. You
will be prompted for a password.
You can use the FX-2000NConfig utility to retrieve the configuration from the dialer by
pressing the Get... button. The Sent/received field will tell you if the configuration you are
viewing is potentially out of date.
The Auto Assign button will automatically assign a UDACT group of the correct type for
every unassigned Input Zone and Output Circuit.