142
master telephone correlation is defined. Master telephone correlation shall be removed
prior to deletion.
Drag & Drop / Copy & Paste
A Fire Phone device cannot be copied if it is already correlated to a selector switch. Doing so
would break the rule of one switch, one phone. If you attempt to copy such a device (or a
loop that contains one) an error message is displayed. If you need to copy phones, do so
with Paste Special and un-check the Copy display correlations option.
Get Job
To access the Get Job feature, you must first connect to the panel and then select Get Job
from the Panel menu, or click on the Get Job button in the Toolbar.
You can get all job data from the panel by using Get Job. This command retrieves a job from
the panel, transposes the data and stores it on the database. If the panel is loaded with an
older version of the firmware, the appropriate size and layout of data structures is built to
receive the data.
If the job is determined to be a newer version of one already stored on the database (it
compares the Job's Globally Unique ID or GUID) then the next highest version is created.
If no prior version of the job is already stored on the database, then a new job is created.
The New Job dialog is used to collect information such as the Job Name, Author and
Comments.
If a job with the same GUID is already on file - meaning that the jobs are of the same
"lineage"- then the New Version dialog is used to collect comments for the version history.
Send Job
To access the Send Job feature, you must first connect to the panel and then select Send
Job from the Panel menu, or click on the Send Job button in the Toolbar.
You can send the current open job to the panel by selecting Send Job from the Panel menu.
The job can be sent to every network node or to selected nodes. This can be useful when
nodes are brought on-line in stages, or if only some nodes need to have their programming
refreshed. However, all nodes of the job must ultimately be programmed with the exact
same job/version.

Table of Contents