7
Configuration
The FleX-Net system, FleX-Net FX-4000 system, and the FX-MNS-6000 network system is
configured using MGC software MSW-036.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, and the
Standard for Control Units for Fire Alarm Systems, CAN/ULC-527-11 certain programming features or
options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Permitted in UL
864/CAN/ ULC-S527-11
(Y/N)
Possible settings Settings permitted in
UL 864/CAN/ULC-
S527-11
Optional Delay of
Transfer from live
paging to alert/alarm
Yes 0 to 20 seconds 0 to 5 seconds
Alarm Transmit
Silence
No Enabled or
Disabled
Disabled or unchecked
Automatic Signal
Silence
Yes
30sec,
1,3,10,15,20,30mi
n
or Disabled
UL minimum 3 minutes
ULC minimum 5
minutes
Powerfail Send
Delay (AC power
trouble signal
transmits to remote
station after this
selected delay)
Yes
0 to 18 Hours
UL 1, 2, 3 Hours
ULC 0, 1, 2, 3 Hours
COPTIR/A Detector
Sensitivity Levels
Yes Levels 1 through 6 Levels 2 through 6
APB-200/COA
Sounder base
correlation to Fire
input
Yes
No sound (no
correlation), Temporal-
3, Temporal-4, March
Code, Maintenance
Chirp, Continuous
Tone
Temporal-3