129
o Two Stage - check to enable two stage. As per UL 864 and UL 2572 only a
setting of Single Stage (disabled) is permissible.
o Primary Node and Secondary Node - options for the Node Control
functionality.
• Network Setting
o Tag - Enter a description for the Network Node. This will appear in the Job
Tree view
o Node Address - Enter the Node address. The control lists all of the available
addresses.
o IP Address - Enter the Internet Protocol (IP) address of this node's Ethernet
connection.
o Subnet mask - This number is combined with the IP Address to identify which
network segment the FX2000N Node is on.
o Default gateway - This is the address of the local IP router that is used to
forward traffic to destinations beyond the local network.
o Supervise Ethernet Connection - If checked, the Ethernet connection on the
Node will be supervised. A trouble will be reported if no Ethernet cable is
plugged into the node.
Note: If not checked, then neither Web Services not BACnet Services can run.
• Graphics Workstation
o Enable - If checked, enables the Graphics Workstation. This enables the panel
to communicate with computer graphical interfaces, like OpenGN. If checked
User may check Supervise Connection.
o Supervise Connection
• Web Services
o Enable - If checked, enables Web Services.
o Activate Web Services – This button allows Web Services license transfer
from the CodeMeter Security Key into the current job. This button will
disappear after Web Services license activation.
o User Name and Password - The user name and password required to access
the Node's web server. If the User Name and Password are edited, the
changes will be applied to all nodes on the job. Also, if new nodes are