Adding Switch Corrs to a Phone
1. Navigate to the addressable loop or Audio Controller phone list view containing
the telephone and highlight it (one phone at a time) in the device list view.
2. Invoke Add Correlations.
3. The Add Correlations dialog appears and presents a list of all of the available
Selector Switches, from all CPUs.
4. Select maximum one switch from each CPU that you want to be associated with
this telephone.
5. Press Add
If you selected more than one switch from the same CPU, then only the first one will be
correlated, and an error message will halt the adding of correlations.
If you had previously correlated one or more switches to this telephone module, then you
will not see any available switches from the same CPU as those existing correlations.
Correlating Phone Module to a Switch Corrs
1. Navigate to the Display Item list containing the Selector Switch and highlight it
(only one switch at a time) in the list view.
2. Invoke Add Correlations.
3. The Add Correlation dialog appears and presents a list of Addressable Phone
Modules and Conventional Phone Circuits. If the Selected switch already has a
correlation, then no available phones are shown.
4. Select only one Phone Module (a switch cannot control more than one
telephone).
5. Press add
If the Phone you selected to add was already correlated to another switch on the same CPU,
you will receive a message "A select switch already exists for control circuit number nnn. A
circuit can only be assigned to one Telephone Switch per CPU".