Function assignment of external
terminal and control
(2) Inverter operation ready signal (RY signal) and inverter running signal (RUN, RUN3 signal)
*1 This signal turns OFF during power failure or undervoltage.
*2 Output is shutoff in conditions like a fault and when the MRS signal is ON.
(3) Fault output signal (ALM, ALM2 signal)
When the inverter is ready to operate, the output of the operation
ready signal (RY) is ON. It is also ON during inverter running.
When the output frequency of the inverter rises to or above
Pr. 13 Starting frequency, the output of the inverter running
signal (RUN) is turned ON. During an inverter stop or DC
injection brake operation, the output is OFF.
The output of the RUN3 signal is ON when the inverter
running and start signals are ON.
(For the RUN3 signal, output is ON if the starting command is
ON even when a fault occurs or the MRS signal is ON.
When using the RY, RUN and RUN3 signals, assign functions to
Pr. 190 to Pr. 196 (output terminal selection function) referring to the
table below.
Inverter
Status
Output
Signal
Start
Signal is
OFF
(during
stop)
Start
Signal is
ON
(during
stop)
Start
Signal is
ON
(during
running)
Under DC
Injection
Brake
Output Shut Off *2
Automatic Restart after
Instantaneous Power Failure
Coasting
Restarting
Start signal
is ON
Start signal
is OFF
Start signal
is ON
Start signal
is OFF
RY ON ON ON ON OFF ON *1 ON
RUN OFF OFF
ON OFF OFF OFF ON
RUN3 OFF
ON ON ON ON OFF ON OFF ON
REMARKS
RUN signal is assigned to the terminal RUN in the initial setting.
If the inverter comes to trip, the ALM and ALM2
signals are output.
The ALM2 signal remains ON during a reset
period after fault occurrence.
When using the ALM2 signal, set "94 (positive
logic)" or "194 (negative logic)" to any of Pr. 190 to
Pr. 196 (output terminal function selection) to assign
the function to the output terminal.
The ALM signal is assigned to the A1B1C1
contact in the initial setting.
REMARKS
Refer to page 330 for the inverter fault description.
RUN
Power
supply
Output frequency
STF
RH
RY
RUN3
Pr. 13
Starting
frequency
Reset
processing
Time
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
DC injection brake
operation point
DC injection
brake
operation
Output
Signal
Pr. 190 to Pr. 196 Setting
Positive logic Negative logic
RY
11 111
RUN
0 100
RUN3
45 145
ON
OFF
ON
ON
OFF
Reset ON
Output frequency
Fault output signal(ALM)
Fault output 2 signal(ALM2)
Reset signal(RES)
OFF
Inverter fault occurrence
(trip)
Reset processing
(about 1s)
Time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)