60
Parameter list
159
Automatic switchover frequency
range from bypass to inverter
operation
0 to 10Hz, 9999 0.01Hz 9999 287
160
User group read selection 0, 1, 9999 1 9999 185
161
Frequency setting/key lock operation
selection
0, 1, 10, 11 1 0 311
Automatic restart
functions
162
Automatic restart after instantaneous
power failure selection
0, 1, 10, 11 1 0 147
163
First cushion time for restart 0 to 20s 0.1s 0s 147
164
First cushion voltage for restart 0 to 100% 0.1% 0% 147
165
Stall prevention operation level for
restart
0 to 120% 0.1% 110% 147
Current
detection
166
Output current detection signal
retention time
0 to 10s, 9999 0.1s 0.1s 130
167
Output current detection operation
selection
0, 1, 10, 11 1 0 130
168
Parameter for manufacturer setting.
Do not set.
169
Cumulative
monitor clear
170
Watt-hour meter clear 0, 10, 9999 1 9999 136
171
Operation hour meter clear 0, 9999 1 9999 136
User group
172
User group registered display/batch
clear
9999, (0 to 16) 1 0 185
173
User group registration 0 to 999, 9999 1 9999 185
174
User group clear 0 to 999, 9999 1 9999 185
Input terminal function assignment
178
STF terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 50, 51, 60, 62,
64 to 67, 70 to 72, 77,
78, 9999
160117
179
STR terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 50, 51, 61, 62,
64 to 67, 70 to 72, 77,
78, 9999
161117
180
RL terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 50, 51, 62, 64 to
67, 70 to 72, 77, 78,
9999
10117
181
RM terminal function selection 11117
182
RH terminal function selection 12117
183
RT terminal function selection 13117
184
AU terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 50, 51, 62 to 67,
70 to 72, 77, 78, 9999
14117
185
JOG terminal function selection
0 to 8, 10 to 14, 16, 24,
25, 37, 50, 51, 62, 64 to
67, 70 to 72, 77, 78,
9999
15117
186
CS terminal function selection 16117
187
MRS terminal function selection 124117
188
STOP terminal function selection 125117
189
RES terminal function selection 162117
Function
Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)