65
Parameter List
Parameter list
4
PARAMETERS
PID control
753
Second PID action selection
10, 11, 20, 21, 40, 41,
50, 51, 60, 61, 70, 71,
80, 81, 90, 91, 100, 101,
110, 111, 120, 121, 140,
141, 9999
1 9999 275
754
Second PID control automatic
switchover frequency
0 to 400Hz, 9999 0.01Hz 9999 275
755
Second PID action set point 0 to 100%, 9999 0.01% 9999 275
756
Second PID proportional band 0.1 to 1000%, 9999 0.1% 100% 275
757
Second PID integral time 0.1 to 3600s, 9999 0.1s 1s 275
758
Second PID differential time 0.01 to 10.00s, 9999 0.01s 9999 275
759
PID unit selection 0 to 43, 9999 1 9999 316
760
Pre-charge fault selection 0, 1 1 0 270
761
Pre-charge ending level 0 to 100%, 9999 0.1% 9999 270
762
Pre-charge ending time 0 to 3600s, 9999 0.1s 9999 270
763
Pre-charge upper detection level 0 to 100%, 9999 0.1% 9999 270
764
Pre-charge time limit 0 to 3600s, 9999 0.1s 9999 270
765
Second pre-charge fault selection 0, 1 1 0
270,
275
766
Second pre-charge ending level 0 to 100%, 9999 0.1% 9999
270,
275
767
Second pre-charge ending time 0 to 3600s, 9999 0.1s 9999
270,
275
768
Second pre-charge upper detection
level
0 to 100%, 9999 0.1% 9999
270,
275
769
Second pre-charge time limit 0 to 3600s, 9999 0.1s 9999
270,
275
PU
774
PU/DU monitor selection 1
1 to 3, 5, 6, 8 to 14, 17,
20, 23 to 25, 40 to 42,
50 to 57, 64, 67, 81 to
86, 100, 9999
1 9999
318
775
PU/DU monitor selection 2 318
776
PU/DU monitor selection 3 318
777
4mA input fault operation frequency 0 to 400Hz, 9999 0.01Hz 9999 177
778
Current input check filter 0 to 10s 0.01s 0 177
779
Operation frequency during
communication error
0 to 400Hz, 9999 0.01Hz 9999 211
799
Pulse increment setting for output
power
0.1kWh, 1kWh, 10kWh,
100kWh, 1000kWh
0.1 1kWh 133
PLC function
826
to
865
Parameter 11 to 50 for user 0 to 65535 1 0 255
867
AM output filter 0 to 5s 0.01s 0.01s 142
869
Current output filter 0 to 5s 0.01s 0.02s 142
870
Speed detection hysteresis 0 to 5Hz 0.01Hz 0Hz 128
872
Input phase loss protection selection 0, 1 1 0 157
Regeneration avoidance function
882
Regeneration avoidance operation
selection
0, 1, 2 1 0 294
883
Regeneration avoidance operation
level
300 to 800V 0.1V
760V/
785VDC
294
884
Regeneration avoidance at
deceleration detection sensitivity
0 to 5 1 0 294
885
Regeneration avoidance
compensation frequency limit value
0 to 30Hz, 9999 0.01Hz 6Hz 294
886
Regeneration avoidance voltage gain 0 to 200% 0.1% 100% 294
Function
Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)