Maximal time for door opening
Maximal time for opening the doors. When the end switches for the doors
are used (FI-260 or FI-270) opening signal is active until door open signal is
active. I-07 is maximal time in which open signal must apear. If signal does not
apear Door A open err“ or „Door B open error“ occurs.
Maximal time for door closing
Maximal time for closing the doors. When the end switches for the doors are
used (FI-261 or FI-271) closing signal is active until door close signal is active.
I-08 is maximal time in which door signal must apear. If signal does not apear
„Door A close err“ or „Door B close error“ occurs.
Maximal time for locking the doors
Represents the time for door locked signal to apear. It is the time from locking
the doors command to signal that the doors are locked. If in this time door
locked signal is not active „door locking err“ occurs.
Temperature for switching off the control board
Parameter for switching off the control board. If the temperature measured
on the procesor reaches the set value the control board is switched off (the
program is not procesed) after the temperature falls below the value set in I-
11 the board is switched on again.
Temperature for switching on the control board
Parameter for setting the temperature for switching on the control panel.