Elevator positioning error messages:
Elevator stopped at the station, 1st station copied, and the lower reference
switch not activated FI-252. Elevator repeats learning travel. Error is
effective for the copy type E-01=2
Possible errors:
- Too many stations copied so elevator stopped in the station without
reference switch.
- Elevator is in the 1st station but there is no reference switch.
- Elevator is not in the 1st station, but the reference signal appeared and
then lost.
Elevator stopped at the station, last station copied, and the upper reference
switch not activated FI-250. Elevator repeats learning travel. Error is
effective for the copying type E-01=2
Possible errors:
- Too many stations copied so elevator stopped in the station withoput
reference switch.
- Elevator is in the last station but there is no reference switch.
- Elevator is not in the last station, but the reference signal appeared and
then lost.
Both upper and lower reference switch active at the same time FI-250 and
FI-252. Switch activity is controled with elevator in the station . After
establishing the logical input state elevator does learning travel. The
message does not indicate during inspection travel and learning travel, if
elevator does not start from the station.
Both upper end lower reference switch for medium speed active at the same
time FI-251 and FI-253, for the copying type E-01=5. Switch activity is
controled with elevator in the station. After establishing the logical input state
elevator does learning travel. The message does not indicate during
inspection travel and learning travel, if elevator does not start from the
station.
Indicates counting downwards switch error, FI-255 for the copying type E-
01=2 or 3. As elevator comes to the lower reference switch, FI-252, system
controls counting downwards. If counting state differs by 2 or more as it
comes to the reference switch, error indicates. Elevator is not blocked but
continues to travel. It is necessary to check the count signals and the lower
reference switch.
Possible errors:
- There is more stations than defined by the parameterA-01.
- Incorrect counting downwards signal.
Indicates counting upwards error, FI-254 for the copying type E-01=2 or 3.
As the elevator comes to the upper reference switch, FI-250, system controls
counting upwards. If counting state differs by 2 or more as it comes to the
reference switch, error indicates. Elevator is not blocked but continues to
travel. It is necessary to check the count signals and the upper reference
switch.
Possible errors:
- There is more stations than defined by the parameter A-01.
- Incorrect counting upwards signal.
Indicates stopping upwards switch deactivation failure FI-256. Entering the
deceleration zone system controls signal activity (must be inactive).
Otherwise, the elevator can not perform the alignment and the preopening
until signal deactivation.
Indicates stopping downwards switch deactivation failure FI-257. Entering
the deceleration zone system controls signal activity (must be inactive).
Otherwise, the elevator can not perform the alignment and the preopening
until signal deactivation.
Indicates copying impulse failure. During drive betwen two stations there
was no change on the input for counting or inductive switch input.