Serial interface (Modbus)
10/05 AWB8230-1541GB
172
10B6 b022 Tripping current for motor
current limitation
rw 0.1 – 1.5 x I
e
for DF51
0.2 – 1.5 x I
e
for DV51
Default, dependent on frequency inverter’s rated
current (Ie)
0.01 [A]
10B7 b023 Motor current limitation,
deceleration time constant
rw 0.1 – 3000 s 0.1 [s]
10B8 b024 Reserved rw
10B9 b025 Reserved
rw
10BA b026 Reserved
rw
10BB b028 Motor current limitation,
limit current selection
rw 00: Value of PNU b022
01: Analog input O-L
10BC b031 Parameter access inhibit
(access rights)
rw 00: Access to all parameters except PNU b031
disabled when digital input SFT is enabled
(a PNU C001: 15)
01: Access to all parameters except PNU b031
and F001 (A020, A220, A021 to A035,
A038) disabled when digital input SFT is
enabled (a PNU C001: 15)
02: Access to all parameters except PNU b031
disabled
03: Access rights to all parameters except
PNU b031 and F001 (A020, A220, A021 to
A035, A038) disabled
10: Extended access rights to parameters in
RUN mode.
10BD b032 Reserved
rw 1 [%]
10BE b034 Reserved
rw
10BF b035 Reserved
rw
10C0 b036 Reserved
rw
10C1 b037 Reserved rw
10C2 b040 Reserved rw
10C3 b041 Reserved rw
10C4 b042 Reserved
rw
10C5 b043 Reserved
rw
10C6 b044 Reserved rw
10C7 b045 Reserved rw
10C8 b046 Reserved rw
10C9 b050 Reserved
rw
10CA b051 Reserved rw
10CB b052 Reserved rw
10CC b053 Reserved rw
10CD b053 Reserved
rw
10CE b054 Reserved
rw
10CF b080 Analog output AM, gain
factor
rw 0 – 255 1 [%]
Holding
register
Function
code
Name Access
rights
Value range Manipulated
variable
hex

Table of Contents