10/05 AWB8230-1541GB
Holding register (word
variable)
173
10D0 b081 Reserved rw – –
10D1 b082 Increased starting frequency
(e.g. with high level of
friction)
rw 0.5 – 9.9 Hz 0.1 [%]
10D2 b083 Carrier frequency rw 2 – 14 kHz 0.1 [%]
10D3 b084 Initializing – function rw 00: Clear fault register –
01: Load default settings (DS)
02: Clear fault register and load default settings
(DS)
10D4 b085 Initialization, country-
specific default settings
rw 00: Japan –
01: Europe
02: USA
10D5 b086 Frequency indication scaling
factor for value in PNU d007
rw 0.1 – 99.9 0.1
10D6 b087 STOP button (keypad) rw 00: Enabled –
01: Disabled
10D7 b088 Motor restart after removal
of the FRS signal
rw 00: Restart with 0 Hz –
01: Restart with the determined output
frequency (current motor speed)
10D8 b089 Indication, value on mains
operation (RS 485)
DF51 only
r 01: Output frequency (d001) –
02: Output current (d002)
03: Direction of rotation (d003)
04: Actual value (PV) (d004)
05: State of digital inputs (d005)
06: State of digital outputs (d006)
07: Scaled output frequency (d007)
10D9 b090 Braking transistor,
permissible percentage duty
factor within a 100 s
interval
DV51 only
rw – 0 – 100 % –
0 – 100 %
0 – 100 %
10DA b091 STOP key, (keypad),
selection of motor stop on
actuation
rw 00: DEC, braking to 0 Hz with deceleration ramp –
01: FRS, free coasting down to 0 Hz
10DB b092 Device fan, configuration
DV51 only
rw 00: The built-in fan is always switched on. –
01: The built-in fan is switched on during
operation (RUN mode); automatic switch-
off 5 min after Stop signal.
02: Built-in fan operation is temperature-
controlled.
10DC b095 Braking transistor, control
DV51 only
rw 00: Function disabled –
01: Enabled in RUN mode
02: Always enabled
Holding
register
Function
code
Name Access
rights
Value range Manipulated
variable
hex