Serial interface (Modbus)
10/05 AWB8230-1541GB
184
! Note: When a fault message is issued, the associated
operational data is saved and can be read with the ENTER
function.
1537 C207 Reserved rw
1538 C208 Reserved rw
1539 C241 Output function – warning
threshold for overload
warning (OL) (second
parameter set)
rw 0 – 2 x Ie [A] Default, dependent on frequency
inverter’s rated current (Ie)
0.01 [%]
153A Reserved
rw
153E
153F H202 Reserved
rw
1540 H203 Motor – assigned rating
[kW]/{HP} at rated voltage
(Ue) (second parameter set)
rw 0.2; 0.4; 0.55; 0.75; 1.1; 1.5; 2.2; 3.0; 4.0; 5.5; 7.5;
11.0 {0.2; 0.4; 0.75; 1.5; 2.2; 3.7; 5.5; 7.5; 11.0}
Default depends on rated voltage and type rating.
1541 H204 Motor – number of poles
(second parameter set)
rw 2, 4, 6, 8
1542 H205 Reserved rw
1543 H206 Motor – stabilization
constant (second parameter
set)
rw 0 – 255 1 [%]
1544 H207 Motor – voltage class
(second parameter set)
DV51 only
rw 200 V (230 V)
400 V
Default, dependent on rated voltage and type rating.
Holding
register
Function
code
Name Access
rights
Value range Manipulated
variable
hex