Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-23
Moeller 07/01 AWB-C2700-1347GB
ALLEN-BRADLEY
PLC Type Protocol PLC Port Parameters
SLC500
DF1 1747-KE 9600 baud, 8 data bits, 1 stop bit, parity even
Full Duplex, BCC checksum
DRIVER DESIGNATION (7, 2) : A.-BRADLEY > SLC-500 (MPB.BIN)
SUPPORTED DATA TYPES : N, B
WIRING LIST
RS 232
Signal Pin Pin Signal
RxD 2 3 TxD
TxD 3 2 RxD
SG 5 5 SG
ZB4-601/609-IF1 DF1-Port
(9 pole male)
(9 pole female)
NOTES
• The 1747-KE communications module from Allen-Bradley is required in order to link the ZB4-601/609-IF1
to the SLC500.
• Configure the DF1 port of 1747-KE using any VT100 terminal (or Windows terminal) for the interface
parameters and type (RS 232) mentioned.
• The parameter setting of the 1747-KE is described in chapter 4 of the manual. The interfaces are set as
standard for RS 232 so that only JW4 for configuring the 1747-KE needs to be set to the required
position.
• Connect the cable with the CONFIG port of the 1747-KE and their VT100 terminal (1200 baud). After the
PLC is switched on, the module responds by activating the menu described in chapter 5. Set the
parameters mentioned for the DF1 port.
• The following parameters are required for the DF1 protocol in addition to the ones mentioned:
FULL-DUPLEX
– Duplicate Packet Detection : Disable
– Checksum : BCC
– Constant Carrier Detect : Disable
– Modem Init String :
– Embedded Response Detect : ADER
– ACK Timeout : 200 ⫻ 5 ms
– ENQuiry Retries : 0
– NAK Received Retries : 0
• The “NODE ADRESS” must correspond with the one to be addressed by the ZB4-601/609-IF1. This is the
address of the SLC500 and not that of the 1747-KE.
The ZB4-601/609-IF1 reports itself as station number 0.