Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-51
Moeller 07/01 AWB-C2700-1347GB
9.3 Hapa
Hapa
PLC Type Protocol PLC Port Parameter
HAPA110
Mininet Mininet 19200 baud, 8 data bits, 1 stop bit, no parity
DRIVER DESIGNATION ALT : HAPA110 > SPOIO Mode (MININET.BIN)
DRIVER DESIGNATION ALT : HAPA110 > PLC Mode (MININET.BIN)
SUPPORTED DATA TYPES : M
WIRING LIST
RS 232 RS 485
Signal Pin Pin Signal
RxD 2 5 TxD-
TxD 3 9 RxD-
SG 5 1 SG
3SG
8RxD+
2RTS
7CTS
ZB4-601/609-IF1 Mininet
(9 pole male)
(9 pole male)
Signal Pin Pin Signal
A3 4TxD+
8RxD+
B7 5TxD-
9RxD-
SG 5 1 SG
ZB4-601/609-IF1 Mininet
(9 pole male)
(9 pole male)
NOTES
• The Hapa110 is connected via the integrated Mininet interface.
The Hapa110 firmware must be created with the appropriate drivers for PLC and SPOIO Mode
(see Hapa110 documentation). The MMI can then be run in one of the two modes.
• The ZB4-601/609-IF1 card must be set to “ALT” and the current Mininet driver (MININET.BIN) must be
loaded (see section 3.1).
• The PLC program does not require any other drivers or interpreters and active communication is started
immediately.
As Mininet is a Master/Slave network, ensure that the destination address of the data block is the same
as that of the PLC. The MMI has the permanently assigned address 0 and is always the master.
• Only marker type “M” can be used with the driver for PLC Mode and SPOIO Mode.
• Each address can either be assigned a byte, word or double word. All values for each address are always
transferred as double words in Motorola format.
Examples :
Byte 5 00 00 00 05 Byte –7 00 00 00 F9
Word 512 00 00 02 00 Word –128 00 00 FF 80
Dword 160 00 00 00 A0 Dword –5430 FF FF EA CA
• The address to be assigned in the MMI also corresponds to the same address in the PLC. For this the
address is multiplied by 4 during data transfer (compatibility with B & R).
• When using the RS 485 variant switch on at least the bus terminating resistors of the ZB4-601/609-IF1.