Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-17
Moeller 07/01 AWB-C2700-1347GB
SIEMENS
PLC Type Protocol PLC Port Parameters
S5
AS511 PG-Port 9600 baud, 8 data bits, 1 stop bit, parity even
DRIVER DESIGNATION (3, 2) : SIEMENS > AS511 (MPB.BIN)
SUPPORTED DATA TYPES : DW
WIRING LIST
TTY
Signal Pin Pin Signal
IN 1 6 OUT+
SG 5 7 OUT-
9IN+
OUT 9 2 IN-
ZB4-601/609-IF1 S5 PG
(9 pole male)
(15 pole male)
NOTES
The interface to the PG-Port of the S5 is the same as for the programming device. No parameter settings
or function blocks are required.
With CPUs that have two interfaces it is best to use the second one since usually not all PG functions are
available on this. All the functions of the ZB4-601/609-IF1 can be implemented with this port.
The PLC must be in Run status for active communication.
If both data blocks or data words are addressed that are not available in the PLC, this will cause errors in
the communication.