Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-28
Moeller 07/01 AWB-C2700-1347GB
8.7 Texas Instruments
TEXAS INSTRUMENTS
PLC Type Protocol PLC Port Parameters
TI500
PG-Port PG-Port 9600 baud, 7 data bits, 1 stop bit, parity odd
DRIVER DESIGNATION (3, 5) : SIEMENS > TI-500 (MPB.BIN)
SUPPORTED DATA TYPES : V
WIRING LIST
RS 422
Signal Pin Pin Signal
TxD+ 2 5 RxD+
RxD+ 3 1 TxD+
SG 5 6 SG
TxD- 7 8 RxD-
RxD- 8 7 TxD-
ZB4-601/609-IF1 TI5xx
(9 pole male)
(9 pole male)
NOTES
• The ZB4-601/609-IF1 is connected to the TI-500 via the PG port. Active communication should be
possible without any further steps.
• Check whether the setting of SW1...12 (in the battery compartment) matches the parameters listed.
SW1 = ON; SW2 = X; SW3...5 = ON; SW6 = OFF; SW7...12 = ON
For switch positions see the cover of the battery compartment or PLC manual.
• The PLC must be switched on and in Run status.