Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-26
Moeller 07/01 AWB-C2700-1347GB
8.6 Matsushita
MATSUSHITA
PLC Type Protocol PLC Port Parameters
FP1
PG-Port PG-Port 9600 baud, 8 data bits, 1 stop bit, parity odd
DRIVER DESIGNATION (8, 1) : MATSUSHITA > FP1/3/5 (MPB.BIN)
SUPPORTED DATA TYPES : DT, R, SV, EV, X, Y
WIRING LIST
RS 422
Signal Pin Pin Signal
DTR+ 1 4 DSR+
TxD+ 2 15 RxD+
RxD+ 3 14 TxD+
DSR+ 4 5 DTR+
SG 5 2 SG
DTR- 6 13 DSR-
TxD- 7 7 RxD-
RxD- 8 6 TxD-
DSR- 9 12 DTR-
ZB4-601/609-IF1 AFP15205
(9 pole male)
(15 pole male)
NOTES
• The ZB4-601/609-IF1 is linked to the FP1 via the AFP15205 converter directly on the PG port of the PLC
(converter = round 15-pole D-sub connector).
• The connection to the PG port of the FP1 is the same as for a programming device and active
communication should be possible without any further steps.
• The PLC must be switched on and in Run status.