Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-45
Moeller 07/01 AWB-C2700-1347GB
8.17 Seitec
SEITEC
PLC Type Protocol PLC Port Parameter
GLT
ISYGLT GLT-Bus 9600 or 38400 baud
8 data bits, 1 stop bit, parity programmed
DRIVER DESIGNATION (9, 2) : USER > GLT 9600 (MPB.BIN)
(9, 4) : USER > GLT 38400 (MPB.BIN)
SUPPORTED DATA TYPES : DW
WIRING LIST
RS 485
Signal Pin Pin Signal
A3 A
SG 5 SG
B7 B
ZB4-601/609-IF1 GLT-Bus
(9 pole male)
(Screw Terminal)
NOTES
• The ZB4-601/609-IF1 interface via GLT-Bus requires the use of a specific module for interpreting
incoming data and copy it to the appropriate markers.
Example : MODULE 1 MDP/B ; ZB4-601/609-IF1 is awaiting on station 1
• This module is a component of the PLC firmware and need no further programming.
• The station number via which the ZB4-601/609-IF1 must report within the network must match the
module number in the PLC program.
• The PLC must be in Run state for active communication.
• If there are more than one ZB4-601/609-IF1 in the network, every ZB4-601/609-IF1 must have his own
station number.
• There are two drivers available one for 9600 baud and one for 38400 baud. Important : Take care that
every module has the same baud rate !
• Also ensure when using RS 485 that the first and the last station in the network have their bus terminating
resistors switched on.