Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-45
Moeller 07/01 AWB-C2700-1347GB
8.17 Seitec
SEITEC
PLC Type Protocol PLC Port Parameter
GLT
ISYGLT GLT-Bus 9600 or 38400 baud
8 data bits, 1 stop bit, parity programmed
DRIVER DESIGNATION (9, 2) : USER > GLT 9600 (MPB.BIN)
(9, 4) : USER > GLT 38400 (MPB.BIN)
SUPPORTED DATA TYPES : DW
WIRING LIST
RS 485
Signal Pin Pin Signal
A3 A
SG 5 SG
B7 B
ZB4-601/609-IF1 GLT-Bus
(9 pole male)
(Screw Terminal)
NOTES
The ZB4-601/609-IF1 interface via GLT-Bus requires the use of a specific module for interpreting
incoming data and copy it to the appropriate markers.
Example : MODULE 1 MDP/B ; ZB4-601/609-IF1 is awaiting on station 1
This module is a component of the PLC firmware and need no further programming.
The station number via which the ZB4-601/609-IF1 must report within the network must match the
module number in the PLC program.
The PLC must be in Run state for active communication.
If there are more than one ZB4-601/609-IF1 in the network, every ZB4-601/609-IF1 must have his own
station number.
There are two drivers available one for 9600 baud and one for 38400 baud. Important : Take care that
every module has the same baud rate !
Also ensure when using RS 485 that the first and the last station in the network have their bus terminating
resistors switched on.