Communications Card Description ZB4-606-IF1, DeviceNet 6-12
Moeller 07/01 AWB-C2700-1347GB
9 Notes
Observe the scan time : It should be approx. 20 ms depending on the quantity of data
At 125 kBaud, 1 ms per frame is assumed. With a 28 Byte module, 4 frames are required in each direction,
making a total of 8 frames. This corresponds to a minimum scan time of 8 ms.
The DeviceNet Scanner must be started explicitely
For this purpose, the respective Bit must be set to “1” in the M-File.