Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-22
Moeller 07/01 AWB-C2700-1347GB
8.5 Allen-Bradley
ALLEN-BRADLEY
PLC Type Protocol PLC Port Parameters
PLC5
DF1 Channel 0 9600 baud, 8 data bits, 1 stop bit, parity even
Full Duplex, BCC checksum
DRIVER DESIGNATION (7, 1) : A.-BRADLEY > PLC-5 (MPB.BIN)
SUPPORTED DATA TYPES : N, B
WIRING LIST
RS 232 RS 422
Signal Pin Pin Signal
RxD 2 2 TxD
TxD 3 3 RxD
SG 5 7 SG
4RTS
5CTS
6DSR
8 DCD
20 DTR
ZB4-601/609-IF1 Channel 0
(9 pole male)
(25 pole male)
Signal Pin Pin Signal
13 CTS+
19 RTS+
RDA 2 14 TxD+
SDA 3 16 RxD+
SG 5 7 SG
SDB 7 3 RxD-
RDB 8 2 TxD-
4RTS-
5CTS-
ZB4-601/609-IF1 Channel 0
(9 pole male)
(25 pole male)
NOTES
Configure the transmission parameters in the PLC5 for channel 0 according to the parameters specified.
The parameters are set in the “MENU ONLINE CONFIGURATION” in the “GENERAL UTILITY” of the
Allen-Bradley programming software:
Channel 0 SYSTEM (point-to-point).
NAK receive 0
DF1 ENQS 0
The “NODE ADRESS” must match the address set for the ZB4-601/609-IF1.
The ZB4-601/609-IF1 itself reports itself as station number 0.
Ensure that all files to be addressed (N and B) are available in the PLC and are large enough.
Addressing files or data words that are not available in the PLC will lead to faulty communication (red
LED “ERROR” lit).