Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-22
Moeller 07/01 AWB-C2700-1347GB
8.5 Allen-Bradley
ALLEN-BRADLEY
PLC Type Protocol PLC Port Parameters
PLC5
DF1 Channel 0 9600 baud, 8 data bits, 1 stop bit, parity even
Full Duplex, BCC checksum
DRIVER DESIGNATION (7, 1) : A.-BRADLEY > PLC-5 (MPB.BIN)
SUPPORTED DATA TYPES : N, B
WIRING LIST
RS 232 RS 422
Signal Pin Pin Signal
RxD 2 2 TxD
TxD 3 3 RxD
SG 5 7 SG
4RTS
5CTS
6DSR
8 DCD
20 DTR
ZB4-601/609-IF1 Channel 0
(9 pole male)
(25 pole male)
Signal Pin Pin Signal
13 CTS+
19 RTS+
RDA 2 14 TxD+
SDA 3 16 RxD+
SG 5 7 SG
SDB 7 3 RxD-
RDB 8 2 TxD-
4RTS-
5CTS-
ZB4-601/609-IF1 Channel 0
(9 pole male)
(25 pole male)
NOTES
• Configure the transmission parameters in the PLC5 for channel 0 according to the parameters specified.
The parameters are set in the “MENU ONLINE CONFIGURATION” in the “GENERAL UTILITY” of the
Allen-Bradley programming software:
Channel 0 SYSTEM (point-to-point).
NAK receive 0
DF1 ENQS 0
• The “NODE ADRESS” must match the address set for the ZB4-601/609-IF1.
The ZB4-601/609-IF1 itself reports itself as station number 0.
• Ensure that all files to be addressed (N and B) are available in the PLC and are large enough.
• Addressing files or data words that are not available in the PLC will lead to faulty communication (red
LED “ERROR” lit).