Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-35
Moeller 07/01 AWB-C2700-1347GB
8.12 Honeywell
HONEYWELL
PLC Type Protocol PLC Port Parameters
IPC620
ABC Comm-Port 9600 baud, 8 data bits, 1 stop bit, no parity
Full duplex
DRIVER DESIGNATION (4, 5) : HONEYWELL > ABC (MPB.BIN)
SUPPORTED DATA TYPES : RG, M
WIRING LIST
RS 422
Signal Pin Pin Signal
TxD+ 2 21 RxD+
RxD+ 3 14 TxD+
TxD- 7 22 RxD-
RxD- 8 15 TxD-
12 RTS+
17 CTS+
13 RTS-
16 CTS-
ZB4-601/609-IF1 Comm-Port
(9 pole male)
(25 pole male)
NOTES
• The MBP-TP is connected to the IPC620 directly on the Comm port or alternatively via a DCM module
with the ABC protocol.
• This interface must be configured with the IPC software beforehand. For this set the Ser. Port to
“Permitted” under “Edit Proc. Conf.” and under “Serial Port Parameters”:
FULL DUPLEX, 9600 baud, No Parity, 1 stop bit, Nodal Address > 0; Protocol ABC.
• The station number set (Nodal address) must correspond to the station number to be addressed via the
ZB4-601/609-IF1.