Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-34
Moeller 07/01 AWB-C2700-1347GB
TELEMECANIQUE
PLC Type Protocol PLC Port Parameter
TSX37
UNI-Telway AUX
AUX (TSX ACC01)
9600 baud, 8 data bits, 1 stop bit, odd parity
DRIVER DESIGNATION (11, 3) : BUS > TELWAY-S (MPB.BIN)
SUPPORTED DATA TYPES : W
WIRING LIST
RS 485
Signal Pin Pin Signal
A3 1A
SG 5 7 SG
B7 2B
ZB4-601/609-IF1 AUX
(9 pole male)
(8 pole MiniDin
male)
NOTES
When the ZB4-601/609-IF1 is connected it is run as a slave and the TSX37 operates as master.
The ZB4-601/609-IF1 can run parallel to the PG in this connection and also with other MMIs. Observe the
more detailed wiring specifications given in the TSX37 manual.
Configure the communication interface of the PLC of CHANNEL0 with the following parameters:
UTW Master, maximum number of slaves (> 3), 9600 baud, Timeout 30 ms
The station number of the TSX27 is always 0 (master).
The stations 1 to 3 are reserved for the PG.
The number of slaves specified must be the same size as the last address in the network.
The station number of the ZB4-601/609-IF1 must always be greater than 3 and smaller or equal to 8, and
is the station number the ZB4-601/609-IF1 reports.
When using the TSX ACC01 ensure that the operating mode selector switch (S1) is set for master mode.
Also ensure that the bus terminating resistors of the first and last stations are switched on.