Communications Card Description ZB4-604-IF1, PROFIBUS-DP 5-9
Moeller 07/01 AWB-C2700-1347GB
7 Layer 7 Profiles
A selection of different profiles are provided in the ZB4-604-IF1 firmware since different PLC manufacturers
normally create their own profiles. A profile driver can be selected for the PLC manufacturer required using
the MV4 configurator. The profile drivers are only specified by a single number which can be entered in the
Select PLC mask under “Profile driver”. If several modules can be selected in a profile use “Modul” to specify
the module required.
7.1 Profile Driver Number 1
The telegram length of this profile is fixed to 15 words.
The words (Motorola notation) are divided as follows:
Data request of the MMI:
Word 0 HB Word 0 LB Word 1 HB Word 2 HB Word 14 LB
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 29
Job number Operation Offset High Offset Low Data Len Data 0 Data n Data 24
The job number is incremented by 1 with every request.
Response of Masters:
Word 0 HB Word 0 LB Word 1 HB Word 14 LB
Byte 0 Byte 1 Byte 2 Byte 29
Job number Status flag Data 0/
Error code
Data n Data 27
The responses of the master contain the same job number as the corresponding request.
Operation codes:
0x10 Read bytes (request information from master)
0x40 Do nothing
0x90 Send bytes (send information to master)
The status flag is reserved for future applications.