EasyManua.ls Logo

Moeller MV4 Series - Mds

Moeller MV4 Series
161 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-40
Moeller 07/01 AWB-C2700-1347GB
8.16 MDS
MDS
PLC Type Protocol PLC Port Parameters
Universal
TP1
TP2
Variable 9600 baud, 8 data bits, 1 stop bit, no parity
DRIVER DESIGNATION (16, 2) : DIVERS > TP1 (MPB.BIN)
(16, 4) : DIVERS > TP2 (MPB.BIN)
SUPPORTED DATA TYPES : DW
WIRING LIST
RS 232 RS 422
Signal Pin Pin Signal
RxD 2 TxD
TxD 3 RxD
SG 5 SG
ZB4-601/609-IF1 Variable
(9 pole male)
Signal Pin Pin Signal
RDA 2 TxD+
SDA 3 RxD+
SG 5 SG
SDB 7 RxD-
RDB 8 TxD-
ZB4-601/609-IF1 Variable
(9 pole male)
RS 485
Signal Pin Pin Signal
A3 A
SG 5 SG
B7 B
ZB4-601/609-IF1 Variable
(9 pole male)
NOTES
The TP protocols are open interfaces to the ZB4-601/609-IF1 and enable data exchange with any PLC
provided with programmable interfaces.
The major difference between the two protocols (TP1 and TP2) is that TP1 transfers individual values and
TP2 data blocks.
For this see the following sections.
The protocol does not require a hardware handshake and can be used with any interface.
The final wiring to your PLC must be made according to the physical interface (see WIRING LIST).