Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-32
Moeller 07/01 AWB-C2700-1347GB
8.11 Telemecanique
TELEMECANIQUE
PLC Type Protocol PLC Port Parameters
TSX17
UNI-Telway TSX-SCG116 9600 baud, 8 data bits, 1 stop bit, parity odd
DRIVER DESIGNATION (11, 3) : BUS > TELWAY-S (MPB.BIN)
SUPPORTED DATA TYPES : W
WIRING LIST
RS 485
Signal Pin Pin Signal
A3 14A
SG 5 8 SG
B7 7B
5Earth
12 UTW
Coding example : 4 Parity
11 N4 (16)
SCG116 as Master 3 N3 (8)
(Station number 0) 10 N2 (4)
2N1 (2)
9N0 (1)
ZB4-601/609-IF1 TSX-SCG116
(9 pole male)
(15 pole male)
“Parity” also be connected to “Earth” if the
number of the “Nx” connected to earth is
even.
Detailed notes on the address coding are
given in the manual on the UNI-Telway Bus
(TSX D24 004G).
NOTES
With this connection the ZB4-601/609-IF1 is run as a slave and the SCG116 acts as master.
Configure the communication module using the dialogue block as described in the manual on the TSX
SCG116 (section 3.1-2), using the following parameters :
UTW Master (exact number of slave), 9600 baud, Timeout 30 ms
The station number of the master is always 0.
The number of slaves defined must be as high as the last address in the network. The station number of
the ZB4-601/609-IF1 in this case must be higher than 0 and corresponds to the station number via which
the ZB4-601/609-IF1 has logged on.
The “NET” and “ADR” LEDs of the TSX SCG116 must not be lit.
If the “ADR” LED is lit, this means that the wired address is not correct. If “NET” is lit, this means that one
or several configured stations are not responding.