Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-29
Moeller 07/01 AWB-C2700-1347GB
8.8 Elin Eldatic
ELIN ELDATIC
PLC Type Protocol PLC Port Parameters
MC1
ECS2000 PG-Port 9600 baud, 8 data bits, 2 stop bit, no parity
DRIVER DESIGNATION (10, 1) : OTHERS > ELIN-MC1 (MPB.BIN)
SUPPORTED DATA TYPES : V, X, Y, I, E, A
WIRING LIST
RS 232
Signal Pin Pin Signal
RxD 2 3 TxD
TxD 3 2 RxD
SG 5 5 SG
ZB4-601/609-IF1 Eldatic MC1
(9 pole male)
(9 pole female)
NOTES
• The ZB4-601/609-IF1 is connected to the Eldatic MC1 directly via the PG port. Active communication
should be possible without any further steps.
• The ZB4-601/609-IF1 has the status of a charging device with the station number 253.
• Data can only be exchanged with the PLC connected (point-to-point) and the number of the connected
stations to be addressed must match.
• Is the data to be exchanged (V, X, Y, I, E, A) actually present in the PLC?
• Are the transmission parameters correctly set?
9600 baud in the “ORG” menu under “Communication” (check via “LAD” menu)
• The PLC must be switched on and must be in Run status.