Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-52
Moeller 07/01 AWB-C2700-1347GB
9.4 Moeller PS40
The interface to Moeller PLCs is described in the manual AWB-C2700-1349GB.
Moeller PS40
PLC Type Protocol PLC Port Parameter
PS4-141
PS4-151
PS4-201
PS4-341
PS416
Suconet K Suconet K
SBI (PS416)
375 kbaud or 187.5 kbaud
DRIVER DESIGNATION ALT : PS4-141-MM1 > Suconet K (PS40.BIN)
DRIVER DESIGNATION ALT : PS4-151-MM1 > Suconet K (PS40.BIN)
DRIVER DESIGNATION ALT : PS4-201-MM1 > Suconet K (PS40.BIN)
DRIVER DESIGNATION ALT : PS4-341-MM1 > Suconet K (PS40.BIN)
DRIVER DESIGNATION ALT : PS416 > Suconet K (PS40.BIN)
SUPPORTED DATA TYPES : M, MB, MW, (MD with PS4-341-MM1 and PS416)
WIRING LIST
RS 485 RS 485
Signal Pin Pin Signal
A3 4A
SG 5 3 SG
B7 1B
ZB4-601/609-IF1 PS4-XXX
(9 pole male)
(5 pole DIN male)
Signal Pin Pin Signal
A3 3A
SG 5 5 SG
B7 7B
ZB4-601/609-IF1 PS416
(9 pole male)
(9 pole male)
Type: ZB4-231-KB1 Type: ZB4-233-KB2
NOTES
Devices with the ZB4-601/609-IF1 card are incorporated in the Suconet network configuration under the
general name “MV4” (Suconet Identifier A060).
The number of Suconet data bytes and the station number of these devices can be parameterised in the
network configuration and must match the settings in the design software:
Sucosoft Topology Configuration Design software
Station number = MMI Station No.
Receive data = Send Buffer
Send data = Receive Buffer
Example configuration with corresponding user data:
Receive data 13 21 37 69
Send data 10 18 34 66
= User data 8 163264