Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-13
Moeller 07/01 AWB-C2700-1347GB
8 BCI 1.0 Drivers
8.1 Mitsubishi
MITSUBISHI
PLC Type Protocol PLC Port Parameters
A series
Computer Link AJ71C24
Format 1 (Mode 1)
9600 baud, 8 data bits, 1 stop bit, no parity
Checksum on
DRIVER DESIGNATION (2, 1) : MITSUBISHI > AJ71C24 (MPB.BIN)
SUPPORTED DATA TYPES : M, D
WIRING LIST
RS 232 RS 422
Signal Pin Pin Signal
RxD 2 2 TxD
TxD 3 3 RxD
DTR 4 6 DSR
SG 5 7 SG
DSR 6 20 DTR
8 DCD
4RTS
5CTS
ZB4-601/609-IF1 AJ71C24
(9 pole male)
(25 pole male)
Signal Pin Pin Signal
TxD+ 2 RxD+
RxD+ 3 TxD+
SG 5 SG
TxD- 7 RxD-
RxD- 8 TxD-
ZB4-601/609-IF1 AJ71C24
(9 pole male)
NOTES
• Check in accordance with the manual for the Computer Link Module AJ71xx whether the mentioned
parameters and interface (RS 232 or RS 422) are correctly set.
Note: the switch assignment is not identical for all AJ71xx!
• Select protocol format 1 for the AJ71xx and station number 0.
• Remember that changes to settings on the AJ71xx are not effective until the PLC has been restarted.
• Correct data transmission on the AJ71xx using RS 232 is indicated by the flashing of LEDs 2SD and
2RD, and LEDs 4SD and 4RD when using RS 422.