Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-13
Moeller 07/01 AWB-C2700-1347GB
8 BCI 1.0 Drivers
8.1 Mitsubishi
MITSUBISHI
PLC Type Protocol PLC Port Parameters
A series
Computer Link AJ71C24
Format 1 (Mode 1)
9600 baud, 8 data bits, 1 stop bit, no parity
Checksum on
DRIVER DESIGNATION (2, 1) : MITSUBISHI > AJ71C24 (MPB.BIN)
SUPPORTED DATA TYPES : M, D
WIRING LIST
RS 232 RS 422
Signal Pin Pin Signal
RxD 2 2 TxD
TxD 3 3 RxD
DTR 4 6 DSR
SG 5 7 SG
DSR 6 20 DTR
8 DCD
4RTS
5CTS
ZB4-601/609-IF1 AJ71C24
(9 pole male)
(25 pole male)
Signal Pin Pin Signal
TxD+ 2 RxD+
RxD+ 3 TxD+
SG 5 SG
TxD- 7 RxD-
RxD- 8 TxD-
ZB4-601/609-IF1 AJ71C24
(9 pole male)
NOTES
Check in accordance with the manual for the Computer Link Module AJ71xx whether the mentioned
parameters and interface (RS 232 or RS 422) are correctly set.
Note: the switch assignment is not identical for all AJ71xx!
Select protocol format 1 for the AJ71xx and station number 0.
Remember that changes to settings on the AJ71xx are not effective until the PLC has been restarted.
Correct data transmission on the AJ71xx using RS 232 is indicated by the flashing of LEDs 2SD and
2RD, and LEDs 4SD and 4RD when using RS 422.