Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-14
Moeller 07/01 AWB-C2700-1347GB
MITSUBISHI
PLC Type Protocol PLC Port Parameters
AX series
Port
Communication
PG-Port 9600 baud, 8 data bits, 1 stop bit, parity odd
Checksum on
FX series
Direct Access PG-Port 9600 baud, 7 data bits, 2 stop bit, parity even
Checksum on
DRIVER DESIGNATION (2, 2) : MITSUBISHI > PG-AX (MPB.BIN)
(2, 3) : MITSUBISHI > PG-FX (MPB.BIN)
SUPPORTED DATA TYPES : M, D
WIRING LIST
RS 422
Signal Pin Pin Signal
DTR+ 1 4 DSR+
TxD+ 2 2 RxD+
RxD+ 3 3 TxD+
DSR+ 4 5 DTR+
DTR- 6 17 DSR-
TxD- 7 15 RxD-
RxD- 8 16 TxD-
DSR- 9 18 DTR-
SG 5 7 SG
21 Pres
ZB4-601/609-IF1 PG AX/FX
(9 pole male)
(25 pole male)
NOTES
• No special notes;
The connection is the same as for the programming device provided that all parameters are fitted and no
other driver or configuration is required in the PLC.