Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-25
Moeller 07/01 AWB-C2700-1347GB
ALLEN-BRADLEY
PLC Type Protocol PLC Port Parameter
SLC503
SLC504
DF1 PROG.TERM 9600 baud, 8 data bits, 1 stop bit, parity even
Full Duplex, BCC checksum
DRIVER DESIGNATION (7, 3) : A.-BRADLEY > SLC503/504 (MPB.BIN)
SUPPORTED DATA TYPES : N, B
WIRING LIST
RS 232
Signal Pin Pin Signal
RxD 2 3 TxD
TxD 3 2 RxD
SG 5 5 SG
ZB4-601/609-IF1 PROG.TERM
(9 pole male)
(9 pole female)
NOTES
Configure the transmission parameters in the SLC503/4 the interface PROG.TERM (Channel 0)
according to the parameters specified.
The parameters are set in the “MENU ONLINE CONFIGURATION” in the “GENERAL UTILITY” of the
Allen-Bradley programming software :
System Channel 0 : FULL DUPLEX
NAK receive 0
DF1 ENQS 0
The “DESTINATION ADRESS” (= PLC) must match the address set for the ZB4-601/609-IF1.
The “SOURCE ADRESS” reports to the ZB4-601-IF1 is fixed as 0 .
Ensure that all files to be addressed (N and B) are available in the PLC are large enough. Addressing
files that are not available, will lead to faulty communication (red Led “ERROR” lit).
If you are also using the same interface “PROG.TERM” for the programming, the parameter are change
always only in the menu “ONLINE” and after in the “ONLINE CONFIG” menu.
In this case the programming cable is identically with the described communications cable.