Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-18
Moeller 07/01 AWB-C2700-1347GB
SIEMENS
PLC Type Protocol PLC Port Parameters
S5-103
R3964R CP521-SI 9600 baud, 8 data bits, 1 stop bit, parity even
DRIVER DESIGNATION (3, 4) : SIEMENS > CP521-SI (MPB.BIN)
SUPPORTED DATA TYPES : DW
WIRING LIST
RS 232 TTY
Signal Pin Pin Signal
RxD 2 2 TxD
TxD 3 3 RxD
SG 5 7 SG
ZB4-601/609-IF1 CP521-SI
(9 pole male)
(25 pole male)
Signal Pin Pin Signal
IN 1 18 OUT+
SG 5 21 OUT-
9IN+
OUT 9 10 IN-
ZB4-601/609-IF1 CP521-SI
(9 pole male)
(25 pole male)
NOTES
The AG103 with the CP521-SI supports the R3964R protocol.
An interpreter with a scaled-down version of DK512 (max 4 data byte) can be obtained for this PLC from
Moeller.
If the interpreter is implemented in the PLC (see appropriate documentation), the ZB4-601/609-IF1 is
capable of implementing RECEIVE and FETCH jobs as with the CP524.
The PLC must be in Run status for active communication.
If both data blocks or data words are addressed that are not available in the PLC, this will cause errors in
the communication.