Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-16
Moeller 07/01 AWB-C2700-1347GB
NOTES
Configure the communications processor used for the specified parameters and select the low priority for
the PLC.
Do not program any jobs for your CP but simply use the standard function blocks (RECEIVE_ALL and
FETCH_ALL). The ZB4-601/609-IF1 cannot accept jobs that are initiated by the CP.
For active data exchange with the CP the function blocks mentioned must be called up in the main
program of the PLC (OB1).
Remember that this interface is not only for the R3964R protocol but also requires the DK512 (= RK512)
data interpreter.
Example:
The CPU944 can run the R3963R protocol on the second interface using the 6ES5-816-1BB21 module.
This only enables data transport, however, the interpreter would have to be implemented in the control
program of the PLC (not recommended).
Note: this CPU can also process the AS511 protocol on the second interface.
PLC and CP must both be in Run status.
If data blocks or data words are addressed that are not available in the PLC, this will cause errors in the
communication.