Communications Card Description ZB4-604-IF1, PROFIBUS-DP 5-12
Moeller 07/01 AWB-C2700-1347GB
Response format: Data direction PLC –> PCS
Byte Designation Description
1 Job number Copy from job (MMI –>PLC)
2 Status 0 Job correctly executed
1 Data type not supported
2 Station address invalid
3 Extended station address invalid
4 Module address not available
5 Start address not available
6 User data volume outside of valid range
3 Reserve
4 ByteCount Number of user data bytes
5 Data 1 User data 1 to n (depending on block size selected from GSD file)
6 Data 2
...
n + 4 Data n
The job is completed when the "Job number“ response = "JobNumber"“. If Status field <> 0, the subsequent
fields have no meaning.
The "JobNumber" field must be written last to ensure data consistency.