Device Description MV4-570-TA1/2, MV4-590-TA1/2 2-7
Moeller 07/01 AWB-C2700-1347GB
Ambient conditions
Operation 0 to 50 °C, 10 to 90 % rel. air humidity,
non-condensing
Storage –20 to 60 °C, 10 to 90 % rel. Air humidity,
non-condensing
Mech. shock IEC 60 068-2-27 (1 shock, half sinus 50 g/20 ms)
Vibration IEC 60 068-2-6 (10 TO 200 TO 10 HZ/1.5 G)
EMC compliance IEC/EN 61 000-4-2, 6 kV/8 kV
IEC/EN 61 000-4-3, 10 V/m
IEC/EN 61 000-4-4, 2 kV
IEC/EN 61 000-4-5, 1 kV/2 kV (AC Version only)
IEC/EN 60 801-6, 10 V
EMF
IEC/EN 61 000-4-8, 10 A/m
Radio interference voltage CISPR 11, EN 55 011, Class A (AC Version only)
Emitted interference CISPR 11, EN 55 011, Class A
Degree of protection (front) IP 65 (NEMA 12), to IEC/EN 60 529
Degree of protection, rear IP 20
Front
Glass 3.0 mm, anti-reflective
Weight
10.4″
approx. 4.8 kg
13.8″
approx. 6.9 kg
Dimensions
Front
10.4″ Device
342 x 270 mm
13.8″ Device
460 x 350 mm
System power AC Versions (MV4-570/590-TA2)
supply
Rated voltage
100 to 240 V AC
Voltage range 85 to 264 V AC
Rated frequency 50 to 60 Hz
Power consumption 40 W max.
Fuse 1.0 AT, externally accessible
DC Versions (MV4-570/590-TA1)
Rated voltage 24 V DC
Voltage range 24 V DC to DIN EN 61 131-2
20.4 to 28.8 V DC effective,
absolute value with ripple 18.5 to 30.5 V
Power consumption 40 W max.
Current consumption 1.0 A norm.
Fuse 4.0 AT, externally accessible
Inrush current 3.0 A
2
s max.
Interfaces/Slots
2 slots for communication modules (Slot 0, Slot 1)