ioLogik E2210 User’s Manual Using ioAdmin
3-9
Power On Settings
Use this field to set the initial behavior of the DI/O channel when the ioLogik E2210 is powered on. For
DI channels in Event Counter mode, you may configure whether or not counting begins at power up. For
DO channels in DO mode, you may configure whether or not the DO is set to OFF or ON at power up. For
DO channels in Output Pulse mode, you may configure whether or not the pulse output commences at
power up.
Safe Status Settings
Use this field to specify how the DI/O channel behaves when the network connection is lost. When the
network connection is lost for the amount of time specified in the Host Connection Watchdog, the ioLogik
E2210 enters Safe Status, and each DI/O channel’s Safe Status settings will go into effect. Note that the
Host Connection Watchdog is disabled by default. If the Host Connection Watchdog is disabled, the
ioLogik E2210 will never enter Safe Status and the Safe Status settings will have no effect.
For DI channels in Event Counter mode, you can configure whether or not counting starts or continues
when Safe Status has been activated. For DO channels in DO mode, you can configure whether or not the
DO is set to OFF or ON at Safe Status. For DO channels in Output Pulse mode, you can configure whether
or not the output pulse commences or continues at Safe Status.
Test I/O
You may test the DI/O channel by using ioAdmin.
.
DI-DI: depends on the device
DI-Counter: start or stop the counter
DO-DO: set the DO to “ON” or “OFF”
DO-Pulse: activate or stop pulse generation.