ioLogik E2210 User’s Manual Click&Go Logic
5-15
At 192.168.127.154
Rule 0: Send I/O status to 192.168.127.3
1. In ioAdmin, make sure that you have searched for and selected the correct ioLogik E2210 server, at
IP address 192.168.127.154. Also, make sure you are logged in on the Server Settings tab. Go to the
Click&Go Logic tab.
2. Double click on #0 in the Rules List. The rule configuration window will appear.
3. Make sure that Enable in the upper left hand corner is checked.
4. Select Enable peer-to-peer I/O
5. Select Input channels mirror to and click remote IP
6. In the 1. Dest. IP: field, enter 192.168.127.3 and click OK to save this setting.
7. Click OK to finish configuring the rule.
8. Click on Download on the Ruleset Management Bar.
9. Select Ye s when asked to restart and wait until the server has restarted and is back on-line.
10. Log in on the Server Settings tab, then go to the Click&Go Logic tab.
11. Click on Run on the Ruleset Management Bar. The RDY LED will be flashing green, showing
that the server is now operating as an Active Ethernet I/O server, using the ruleset that was just
defined.
At 192.168.127.3
Rule 0: DI(0) at 192.168.127.154 mapped to DO(0)
Rule 1: DI(1) at 192.168.127.154 mapped to DO(1)
1. In ioAdmin, make sure that you have searched for and selected the correct ioLogik E2210 server, at
IP address 192.168.127.3. Also, make sure you are logged in on the Server Settings tab. Go to the
Click&Go Logic tab.
2. Double click on #0 in the Rules List. The rule configuration window will appear.
3. Make sure that Enable in the upper left hand corner is checked.
4.
Select Enable peer-to-peer I/O
5. Select Output channel, then select DO-0 for the first field, enter 192.168.127.154 for the second
field, and select DI-0 for the third field.
6. Click OK to finish configuring the rule.
7. Double click on #1 in the Rules List. The rule configuration window will appear.
8. Make sure that Enable in the upper left hand corner is checked.
9. Select Enable peer-to-peer I/O
10. Select Output channel, then select DO-1 for the first field, enter 192.168.127.154 for the second
field, and select DI-1 for the third field.
11. Click OK to finish configuring the rule.
12. Click on Download on the Ruleset Management Bar.
13. Select Ye s when asked to restart and wait until the server has restarted and is back on-line.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E2210 and is the answer not in the manual?

Moxa Technologies ioLogik E2210 Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E2210
CategoryI/O Systems
LanguageEnglish

Related product manuals