ioLogik E2210 User’s Manual Click&Go Logic
5-16
14. Log in on the Server Settings tab, then go to the Click&Go Logic tab.
15. Click on Run on the Ruleset Management Bar. The RDY LED will be flashing green, showing
that the server is now operating as an Active Ethernet I/O server, using the ruleset that was just
defined.
Sensors at the water tank will connect to digital input channels at 192.168.127.154, and the digital output
channels at 192.168.127.3 will connect to the control panel. As long as both ioLogik E2210’s are on and
connected to the network, the status of digital output channels 0 and 1 at 192.168.127.3 will be a “mirror”
of input channels 0 and 1 at 192.168.127.154. Status will be updated once every second.