EasyManua.ls Logo

Omni 7000 Series - Page 181

Omni 7000 Series
191 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OMNI 4000/7000 Installation Guide Rev H
Page A-3
Jumper Settings
Input Channels 1 and 2 can accept:
Analog input voltages (1-5 VDC)
Current inputs (4-20mA) converted to 1-5 VDC by installing the 4-20 jumper
Low level RTD input signals (0.200.55 VDC)
Installing the RTD jumper increases the signal input by a factor of 10X.
Input Channels 3 and 4 can accept:
Analog input voltages (1-5 VDC)
Current inputs (4-20mA) converted to 1-5 VDC by installing the 4-20 jumper
Pulse signals (0-12 kHz) by removing the four “A” jumpers and installing the two “P” jumpers
Input Channel 4 can be configured for AC or DC signal coupling. The input signal trigger
threshold can be lowered from 3.5 to 1.5 VDC by removing the input threshold HI jumper, which
makes it suitable for interfacing to Solartron type densitometers.
A.3 A/B Module Setup
Configure the A/B Combo as either an A module or a B module by positioning the TYPE jumper
(JPB) as indicated in Figure A-1.
Assign a unique address to each A or B module installed into the OMNI flow computer by
positioning the jumpers address (ADD) in the jumper table as indicated in Figure A-1.
Figure A-1: A Module Type and Address Jumpers
JPB
2
A1
A2
A0
1
A1
A2
A0
5
6
A1
A2
A0
3
4
ADDRESS
TYPE A
B
JPB
A1
A2
A0
JUMPER TABLE
JUMPERS
ADDRESS
ADDRESS

Table of Contents

Other manuals for Omni 7000 Series

Related product manuals