5-45
5 Installation
CJ2 CPU Unit Hardware User’s Manual
5-4 Control Panel Installation
5
5-4-5 Electrical Environment
To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
Power cables and signal cables adversely affect each other. Do not wire them in parallel.
Noise induction may occur if the PLC is installed in a panel that includes high-voltage devices.
Whenever possible, wire and install them separately. (Refer to PLC Installation Location on page
42.)
Either install the PLC a minimum of 200 mm from high-voltage lines or power lines, or place the
high-voltage lines or power lines in metal tubing and completely ground the metal tubing to 100
or less.
z Other Precautions
Basic I/O Units have both plus and minus commons, so pay attention to the polarity when wiring.
Optical fiber cable looks like ordinary communications cable or power cable, but internally it con-
sists of fibers, tension members, other protective materials. It must be handled with care. In partic-
ular, optical fiber cable must be installed according to prescribed methods and standards. Do not
subject optical fiber cable to severe tensile shock, excessive bending, twisting, or excessive con-
striction. For details on wiring optical fiber cables, refer to the following manuals.
SYSMAC H-PCF Optical Fiber Cables Installation Guide (Cat. No. W156)
Optical Ring Controller Link Units Operation Manual (Cat. No. W370)
Parallel Wiring (Single Phase)
Correct
Correct
Power supply
Incorrect
Power supply
Power supply
Load
Load
Load
Example: Separating PLC from Power Lines
PLC
Metal tubing
PLC
200 mm
200 mm
Panel with power line
Power line
Ground of 100 or less
Power line