6 Troubleshooting
6-12
CJ2 CPU Unit Hardware User’s Manual
z Cycle Time Too Long
A cycle time too long error will occur if the PLC cycle time exceeds the setting for Watch Cycle Time
in the PLC Setup.
z Error Causes and Remedies
z Peripheral Servicing Too Long
This error will occur if the peripheral servicing time exceeds 2.0 s.
z Error Causes and Remedies
Cycle Time Too Long (Fatal Error)
POWER RUN ERR/ALM
CX-Program-
mer display
Error flag Error code
Error infor-
mation
Lit. Not lit. Lit. Cycle Time
Error
A401.08 809F None
Suspected cause of
error
Confirmation method Remedy
Prevention of recur-
rence
An interrupt task with a
long processing time was
executed.
Check the Max. Interrupt
Task Processing Time
(A440)
Divide the interrupt task
into sections.
Same as at the left.
An incorrect value (an
extremely large number)
was set for the number of
repeats of FOR(512).
Set up a trap in the ladder
program to monitor the
number of repeats.
Correct the ladder pro-
gram.
Same as at the left.
POWER RUN ERR/ALM
CX-Program-
mer display
Error flag Error code
Error infor-
mation
Lit. Not lit. Lit. Cycle Time
Error
A405.15 809F ---
Suspected cause of
error
Confirmation method Remedy
Prevention of recur-
rence
The event load was too
high.
--- Reduce the event load. Same as at the left.

Table of Contents

Other manuals for Omron CJ2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ2 and is the answer not in the manual?

Omron CJ2 Specifications

General IconGeneral
ModelCJ2
ManufacturerOmron
TypeProgrammable Logic Controller (PLC)
CPU UnitsMultiple models available (e.g., CJ2M, CJ2H)
Number of I/O PointsUp to 2, 560 points
Communication PortsEthernet/IP, EtherCAT, USB, Serial
ExpansionYes, via I/O Units and Special I/O Units
I/O Control MethodCyclic Scan, Interrupt
Programming LanguageLadder diagram, structured text, function block diagram, sequential function chart, instruction list
Built-in I/OAvailable on some models (e.g., CJ2M)
Ethernet PortYes, 1 port (depending on CPU Unit)
Serial PortsRS-232C, RS-422/485 (configurable)
USB PortYes (for programming and monitoring)
Operating Temperature0°C to 55°C
Storage Temperature-25 to 70°C
Humidity10 to 95% RH (non-condensing)
Vibration Resistance10 to 57 Hz, Amplitude: 0.075 mm, 57 to 150 Hz, Acceleration: 1 G, X, Y, and Z directions, 80 min each
Power Supply Voltage24 VDC or 100 to 240 VAC (depending on CPU Unit)