25.11 Disable / re-enable alert annunciation
function (H2/B11)
Normal operation:
For alarm points / zones programmed for Alert Annunciation (via
EBLWin) is normally the AA function enabled via a time channel, e.g.
enabled daytime (during working hours) and disabled night time.
As an alternative, the AA function can be continuously enabled.
Turned Off
Via this menu (H2/B11) it is possible to disable the AA function, i.e.
the AA function will be disabled for the alarm points / zones
programmed for Alert Annunciation in spite of the time channel is
"on" or if they are programmed to be continuously enabled.
The AA function will stay disabled until re-enabled again via this
menu.
NOTE! Disabled Alert Annunciation function is not indicated by
LED "Disablements" (L8).
The LED "Fault / Disablements Fire brigade tx delay" (L16) turned
off, is indicating that the Alert Annunciation function is turned off by
a time channel or is disabled via this menu.