Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
97
25.10 Disable / re-enable outputs for routing
equipment (H2/B10)
Disabled outputs are listed in menu H4/U1.
Outputs for routing equipment (fire brigade tx / fault tx) can be
disabled and re-enabled via this menu. Disabled output will stay
disabled, until re-enabled again via this menu.
Can be useful during an installation and test period, when only local
alarms are required.
Disabled output is indicated by LEDs "Disablements" (L8) and "Fault
/ Disablements Fire brigade tx" (L15).
According to chapter
"Access", see page 81.
Disable or re-enable
ACCEPT? H2
Disable / re-enable outputs for
routing equipment ACCEPT? B10
Routing equipment for FIRE:1, FAULT:1
(1=enabled, 0=disabled) ACCEPT?
To move the cursor, press
"". Edit and/or press "A"
to accept.
All outputs to routing equipment for:
FIRE is disabled / FAULT is enabled
Routing equipment for FIRE:0, FAULT:1
(1=enabled, 0=disabled) ACCEPT?
Disable / re-enable outputs for
routing equipment ACCEPT? B10
Scroll or press "Return" to
return to H2.
Disable or re-enable
ACCEPT? H2
Scroll or press "Return".