31.6 Test of alarm devices (H8/S6)
The programmable outputs
of type "Alarm device" can be
collectively activated via this sub menu (S6), which makes it possible
to test the alarm devices without too much disturbance on site.
The test cannot be started if fire alarm is already activated in EBL128.
When the test starts, the alarm devices will sound for approx. 1
second, be silent for approx. 29 seconds, sound for approx. 1 second
and so on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
According to chapter
"Access", see page 81.
Acknowledge SERVICE signal
ACCEPT? S1
Test of alarm devices
ACCEPT? S6
Test of alarm devices?
ACCEPT?
Press "A" to start the test.
Test of alarm devices in progress.
End test? ACCEPT?
The test will now
continue until stopped
via this menu (S6) or
automatically after one
hour or if a fire alarm is
activated.
Press "A" to stop the test.
Test of alarm devices?
ACCEPT?
Test of alarm devices
ACCEPT? S6
Scroll or press "Return" to
return to menu H8.
Including Addressable siren 3377 / 4477, Addressable sounder base 3379,
Addressable beacon 4380 and Light indicator 4383.
The output activation will be steady (continuous). For the alarm devices
3377 / 4477 and 3379, the tone with the highest priority level (and type
"alarm device") will be automatically selected.