MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
24
7.1 User level 1
With the door closed, anybody has access to the push button "Alarms
queued" (P1) to scroll / browse through the queued alarms.
7.2 User level 2A
After the door has been opened with the fire brigade key (LED "Door
open" is lit), the user / fire brigade personnel have access to the
following push buttons:
Push
button
Operation/function
P2
Silence the buzzer in the c.i.e.
P3
Silence all alarm devices (sounders).
P4
Reset fire alarms. (see below)
NOTE! Fire alarms are:
Fire alarm (incl. heavy smoke/heat alarm)
Alert Annunciation (AA) alarm
Key cabinet alarm
Co-incidence alarm (if not reset automatically)
Acknowledged alarm (New Zealand only)
Isolated alarm (New Zealand only)