25.2 Disable zone / address (H2/B2)
Up to 100 addressable alarm points (also addressable manual call
points), connected to the COM loop, can be individually disabled.
Disabled alarm points (zone address) are listed in menu H4/U1.
Disabled alarm points (zone address) can be automatically re-
enabled or they have to be re-enabled via menu H2/B6.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 81.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B2.
Disable zone-address
ACCEPT? B2
"A"
Disable zone: 00 Address: 00
ACCEPT?
Write zone number and
address e.g.
"01-01"
Disable zone: 01 Address: 01
ACCEPT?
Press "A" to accept.
"A"
Automatic re-enabling:0 (0=No,1=Yes)
Time: HH:MM ACCEPT?
Press "1" for aut. re-
enabling and accept or
change the time (max. 24
hours).
Press "A" to accept.
LED "Disablements" (L8)
will light up.
(Default is current time + 3 hours)
"A"
Zone 01 address 01 is disabled
"A"
Disable zone: 00 Address: 00
ACCEPT?
If more disablements
shall be done, continue
like above. If not, press
"Return" to menu B2.
"Return"
Disable zone-address
ACCEPT? B2
Scroll or press "Return"
to menu H2.
"Return"
Disable or re-enable
ACCEPT? H2
Scroll or press "Return".