118
28.5 Display current consumption on COM-loop
(H5/A5)
An average current consumption value can be displayed for the COM
loop.
NOTE! No or very small current consumption will not be presented
correctly / precisely since the accuracy is ± 5 mA.
Action
Text in display
Comments
"Access"
According to chapter
"Access", see page 81.
Scroll to menu H5.
Service
ACCEPT? H5
"A"
Calibration of supervised outputs
ACCEPT? A1
Scroll to menu A5
Display current consumption on
COM-loop ACCEPT? A5
"A"
Current consumption on COM-loop is
xxx mA ACCEPT?
"A"
or
"Return"
Display current consumption on
COM loop ACCEPT? A5
Scroll or press "Return" to
H5.
"Return"
Service
ACCEPT? H5
Scroll or press "Return"
NOTE! The window is updated continuously.