8 Silence Alarm devices
In EBL128, on the FBP, there is a push button "Silence Alarm
devices" (P3).
If the push button "Silence Alarm devices" is pressed during a pre-
warning, a fire alarm
or a Co-incidence alarm, the following will
happen:
LEDs "Fire" (L1) and "Alarms queued" (L2)
, programmed for sounders (type Alarm
devices), will be silenced.
In case of a new alarm, or if the push button "Silence Alarm devices"
is pressed again, the sounders will automatically sound again.
NOTE! This is also valid for Pre-warning and Co-incidence alarm.
In EBLWin, the option Button "Silence alarm devices" disables alarm
devices can be selected.
In this case the button "Silence alarm devices" (P3) will have the same
function as in the menu H2/B9, see page 96. See also chapter
"Disable / Re-enable alarm devices", page 32.
In the Australian and New Zealand conventions only, the "FIRE"
LEDs will indicate steady instead of blinking when the alarm devices
are disabled.
Including Addressable siren 3377 / 4477, Addressable sounder base 3379,
Addressable beacon 4380 and Light indicator 4383.