Panasonic Eco Solutions Nordic AB
MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
45
or
*** Fire Alarm ***
ZONE: 14 Time HH.MM Date MM-DD
Alarm text for zone 14
Reset of the fire alarms, see chapter "Alarm reset", page 53.
NOTE!
1. The fire alarm presentation in the EBL128 display is for the
German (VdS) convention only, different than described above.
The serial number for the displayed alarm is deleted and the different
fields on the top row are separated by black squares as follows (an
example):
BER-ADR 12-45 LETZTER BER 12 Nr.01
"Alarm text for 12-45"
2. The fire alarm presentation in the EBL128 display is for the New
Zealand convention only, different than described above.
The serial number for the displayed alarm is replaced with the
information "ALM" as follows (an example):
ALM ZONE-ADDR 13-02 LAST ZONE 13 No. 02
"Alarm text for 13-02"
If the fire alarm is acknowledged (see page 56), "ALM" will be
replaced with "ACK".
If the fire alarm or the acknowledged alarm is isolated (see page 56),
"ALM" will be replaced with "ISO".
16.2.1 Fire alarm menu (X1-X9)
During the fire alarm presentation, a special fire alarm menu can be
used. (If this menu / option is excluded (via EBLWin), it is a violation
to the EN54-2 standard).
Fire alarms can be displayed via this menu but it can also be used to
display faults and disablements in the system.
Alarm points, zones, control outputs and alarm devices can also be
disabled / re-enabled via this menu.
No User name and Password are required.
During the fire alarm presentation press button "Access"
41
and the
alarm text will be replaced with the following:
41
Access code is not required.